This presentation was generated by
Fluor
Hanford for the U.S. Department of Energy.
The main point of this presentation is that the neutral wire (typically white in color)
is unfortunately named in a way that implies it is harmless. Most people know that if you
touch the black (or red or blue) wire, chances are you are going to receive an electrical
shock. They also believe that it is safe to touch the white (neutral wire).
Under most conditions, this is true. However, that is only so if the path your body makes
to ground is a significantly higher resistance to current flow than what the neutral wire
path provides. This requires the neutral wire to have a complete path back to the service
panel. If the neutral wire somehow gets disconnected from the neutral bar in the panel, your
body becomes the only return path to ground for the electrical current.
So, the cardinal law of working around live circuits is to assume that the neutral conductor
is at the same potential as the hot wire. I have worked on many live circuits in my life and
have been bitten a couple times by open neutrals - it is not a good feeling. Just for the
record, the highest AC voltage I have been hit by was a 3-phase 480 V supply to a commercial
welder. The highest DC was from a 2 kV radar CRT display. I have been lucky - no permanent
damage... other than mental :-)
Potential Hazards with Neutral Conductors
Neutrals Are Current Carrying Conductors
- Neutrals are grounded but carry current under load.
- The source of neutral current cannot always be identified.
- Breaking a neutral under load could create a shock hazard.
- Individuals contacting a lifted neutral potentially provide an alternate path to ground.
- A broken neutral or lifted neutral could result in a shock or an arc.
Energized Neutral Examples
- A neutral was misidentified and inadvertently opened creating an arc (ORPS EM-SR-WSRC-FTANK-2005-0009)
- A circuit was moved to a different distribution panel, but the neutral was spliced in
the original panel (ORPS EM-RL-PHMC-PFP-2005-0011)
- An electrician received a shock after lifting a neutral from its bus bar. The neutral
received its power through an emergency light that received power from another distribution
panel. (ORPS SC-PNSO-PNNL=PNNLBOPER-2005-0018)
Configuration That Requires Additional Precautions:
Component Labels
|
Circuit Breaker |
|
|
Circuit A Ungrounded Conductor |
|
Circuit B Ungrounded Conductor |
|
Grounded Conductor (Neutral Conductor) |
|
Ground |
Notes:
- 3 current carrying conductors in a raceway.
- Copper ground wire omitted for simplicity.
- Highlighted in yellow indicates energized.
|
|
Ballast / Fluorescent Light |
|
Ballast / Fluorescent Light enclosure |
The Multi-Wire Branch Circuit is an acceptable configuration according to the National
Electrical Code (NEC) Section 210.4.
The Multi-Wire Branch Circuit
This circuit has also been referred to as:
- The Edison Circuit
- Common Neutral Circuit
- Shared Neutral Circuit
- These circuits are typically found on 120 / 240 volt single phase systems, but can be
found on 208Y /120 and 277Y / 480 volt systems as well.
- The Grounded Neutral wire carries the unbalanced load current. (“Grounded Conductor”)
Use the following guidance when the neutral conductor must be interrupted:
Note: Some of the original PowerPoint slides contained animations, which have been omitted
here. No important information is lost in the process.
|